C-Series
Circuit Breaker
The C-Series hydraulic/magnetic circuit breakers are
ideal for applications that require higher amperage and
voltage handling capability in a smaller package. They are
available in 1-6 poles, 0.02-100amps, UL Recognized up to
480VAC or 150VDC, UL489 Listed up to 240VAC or 125VDC,
with choice of time delays, terminal options, actuator
styles and colors.
HANDLE ACTUATOR METAL TOGGLE ACTUATOR
Product Highlights:
The UL489 C-Series employs a unique arc chute design
which allows for higher interrupting capacities of up to
10,000 amps. New thermoset glass filled polyester half
shell construction provides for increased mechanical
and electrical strength. The wiping contacts, mechanical
linkage with two step actuation, clean contacts
providing high, positive contact pressure and longer
contact life
Available with American Standard or Metric Threaded
Stud terminals, or Saddle Clamp screw terminals.
Optional mid-trip handle style actuator allows visual
indication of electrical overload with or without alarm
feature
PARALLEL POLE ACTUATOR
Agency Certifications:
UL Recognized
|
UL Standard 1077 UL Standard 508
Available with new solid color rocker actuators and
unique two-color Visi-rocker® actuators, which can be
specified to indicate either the ON or TRIPPED/OFF
mode
UL Standard 1500
UL Listed
|
UL Standard 489 UL Standard 489A
|
CSA Accepted CSA Certified
Exclusive Rockerguard and Push-To-Reset bezel help
prevent inadvertent actuation
|
TUV Certified VDE Certified
* For full Agency Certifications, please see pg. 6
Carling Technologies, Inc.
60 Johnson Avenue • Plainville, CT 06062-1177
Phone: (860) 793-9281 • Fax: (860) 793-9231
Email: sales@carlingtech.com • www.carlingtech.com
|
2
C-Series – General Specifications
Electrical Tables
Table A: Lists UL Recognized & CSA Accepted configurations and performance capabilities as a Component Supplementary
Protector
150
150
80-100
TC1, OLO, U3
TC, OLO, U3
Agency Code
L
101-175
Agency Code Parallel Pole
L
Notes for Table A:
1
Requires branch circuit backup with a UL LISTED Type K5 or RK5 fuse rated 15A minimum and no more than 4 times full load amps not to exceed 125A for 50 Amp or less rating and not to
exceed 175 for 51 through 100 Amp rating
*Manufacturer reserves the right to change product specification without prior notice.
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: sales@carlingtech.com • www.carlingtech.com
|
C-Series – General Specifications
3
Electrical Tables
Table B: Lists UL Recognized and CSA Accepted configurations and performance capabilities as a Manual Motor Controller.
RELAY
Notes for Table B:
1
UL recognized and CSA Accepted at 480V refers to 3 & 4 pole versions used in a 3Ø, wye connected circuit or 2-pole version connected with 2 poles breaking. 1Ø and backed up with
series fusing as stated above in note 1.
*
Series, Shunt and Relay Trip - Voltage Coil Construction not current coils
Table C: Lists UL Recognized, CSA Accepted , VDE and TUV Certified configurations and performance capabilities as a
Component Supplementary Protector.
Notes for Table C:
1
2
General Purpose ratings for UL/CSA only.
Requires branch circuit backup with a UL LISTED Type K5 or RK5 fuse rated 15A minimum and no more than 4 times full load amps not to exceed 125A for 50 Amp or less rating and not to
exceed 175 for 51 through 100 Amp rating.
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: sales@carlingtech.com • www.carlingtech.com
|
4
C-Series – General Specifications
Electrical Tables
Table D: Lists UL Listed (489), CSA Certified (C22.2 No. 5.1-M) configuration and performance capabilities as a Molded Case
Circuit Breaker.
C SERIES TABLE D : UL489 LISTED BRANCH CIRCUIT BREAKERS
INTERRUPTING
CURRENT
VOLTAGE
FREQUENCY
DC
CAPACITY
(AMPS)
RATING
CIRCUIT
CONFIGURATION
CONSTRUCTION NOTES
MAX.
RATING
FULL LOAD
AMPS
WITHOUT
BACKUP FUSE
50,0001
10,000
PHASE
---
Limited to 2 Poles Max from 71 - 100 Amps.
80
0.10 - 100
Limited to 2 Poles Max from 71 - 100 Amps.
125
DC
DC
---
---
0.10 - 100
0.10 - 50
0.10 - 50
51 - 70
5,000
5,000
10,000
5,000
5,000
1 - 3 Poles
125 / 250
1 or 2 Poles (2 Poles Required for 250 Volts)
1 - 3 Poles
120
50 / 60
50 / 60
1
1
SERIES
1 - 3 Poles
0.10 - 50
2 or 3 Poles. 1 Pole of a 3 Pole Unit is Neutral
120 / 240
1
10000
2 or 3 Poles. 1 Pole of a 3 Pole Unit is Neutral
0.10 - 50
0.10 - 30
0.10 - 20
0.10 - 20
0.10 - 30
240
240
277
120
50 / 60
50 / 60
50 / 60
50 / 60
1
1
1
1
5,000
5,000
1Pole
2 Pole
1Pole
---
10,000
10,000
DUAL COIL
Notes from Table D:
1
Special catalog number required. Consult factory.
Table E: Lists UL Recognized, CSA Accepted configurations and performance capabilities as Protectors, Supplementary for
Marine Electrical and Fuel Systems (Guide PEQZ2, File E75596). Ignition Protected per UL 1500. UL Classified Small Craft
Electrical Devices, Marine in accordance with ISO 8846 (Guide UZMK, File MQ1515) as Marine Supplementary Protectors.
Table F: Lists UL Listed configurations and performance capabilities as Circuit Breakers for use in Communications Equipment
(Guide DITT, File E189195), under UL489A.
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: sales@carlingtech.com • www.carlingtech.com
|
C-Series – General Specifications
5
Electrical
Mechanical
Endurance
10,000 ON-OFF operations @ 6 per
minute; with rated current & voltage
All C-Series circuit breakers will trip
on overload, even when actuator is
forcibly held in the ON position.
The operating actuator moves
positively to the OFF position when
an overload causes the breaker to
trip. With mid-trip, handle moves to
the mid position on electrical trip
of the circuit breaker. With mid trip
handle with alarm switch, handle
moves to the mid position and
the alarm switch actuates when
the circuit breaker is electrically
tripped.
Maximum Voltage
AC, 480 WYE/277 VAC, 50/60 Hz
(see Table A.)
UL489: AC,240 VAC. (Table D),
50/60 Hz, 125 VDC, UL 1077,
150 VDC, 277 VAC
Trip Free
Trip Indication
Current Rating
Standard current coils: 0.100,
0.250, 0.500, 0.750, 1.00, 2.50,
5.00, 7.50, 10.0, 15.0, 25.0, 30.0,
35.0, 40.0, 50.0, 60.0, 70.0, 80.0,
90.0 and 100 amps. Other ratings
available, see Ordering Scheme.
DC - 6V, 12V; AC - 120V; other
ratings available, see Ordering
Scheme.
SPDT; 10.1 amps-250VAC, DC
Aux. Switch 1.0A, 65 VDC. 0.5A,
80VDC,1/4 HP, 125VAC,VDE & TUV
1.0 125 VAC.
Minimum of 100 Megohms at 500 VDC.
UL, CSA: 1960 V 50/60 Hz for one
minute between all electrically
isolated terminals. C-Series
Circuit Breakers comply with the
8mm spacing and 3750V 50/60
Hz dielectric requirements from
hazardous voltage to operator
accessible surfaces, between
adjacent poles and from main
circuits to auxiliary circuits per
Publications EN 60950 and VDE
0805.
Standard Voltage Coils
Auxiliary Switch Rating
Physical
Insulation Resistance
Dielectric Strength
Number of Poles
1-6 poles ≤ 50A; 1-4 poles @ 51-
70A; 1-2 poles 71-100A. UL489
Handle: 1 pole ≤ 100A, 2 pole ≤
50A; Rocker: 1 pole ≤ 100A.
Internal Circuit Configuration Series (with or without auxiliary
switch, mid trip & mid trip with
alarm switch) Shunt & Relay with
current or voltage trip coils, Dual
Coil, Switch Only (with or without
aux. switch). UL489: Series (with or
without auxiliary switch, mid-trip &
mid-trip with alarm switch).
Weight
Standard Colors
Approx.112 grams/pole ( 3.95 oz).
Housing: Black
Resistance, Impedance Values from Line to Load Terminal
based on Series Trip Circuit
RESISTANCE, IMPEDANCE VALUES
Breaker.
Environmental
from Line to Load Terminals
(Values Based on Series Trip Circuit Breaker )
Designed and tested in accordance with requirements of
specification MIL-PRF-55629 & MIL-STD-202 as follows:
1000
CURRENT
TOLERANCE
(AMPS)
(%)
100
10
Shock
Withstands 100 Gs, 6ms sawtooth
while carrying rated current per
Method 213, Test Condition “I”.
Instantaneous and ultrashort curves
tested @ 90% of rated current.
Withstands 0.060” excursion from
10-55 Hz & 10 Gs 55-500 Hz, @
rated current per Method 204C,
Test Cond. A. Instantaneous &
ultrashort curves tested @ 90% of
rated current.
0.10 - 5.0
5.1 - 20.0
20.1 - 100.0
± 15%
± 25%
± 35%
O
H
M
S
1
Vibration
0.1
0.01
0.001
0.01
0.1
1
10
100
AMPERE RATING
Moisture Resistance
Salt Spray
Method 106D, i.e., ten 24-hour
cycles @ +25°C to +65°C, 80-98%
RH.
Method 101, Condition A (90-95%
RH @ 5% NaCl Solution, 96 hrs).
Method 107D, Condition A (five
cycles @ -55°C to +25°C to +85°C
to +25°C).
Pulse Tolerance Curves
60 Hz 1/2 Cycle
50 Hz 1/2 Cycle
Inrush Pulse Tolerance
Inrush Pulse Tolerance
I
I
r
r
Time Delay Curves
Time Delay Curves
42, 44 46
(50 Amps Max.)
&
22x
10x
42, 44 & 46
(50 Amps Max.)
25x
12x
Time Delay Curves
22, 24 (100 Amps Max.)
26 (70 Amps Max.)
Time Delay Curves
22, 24 (100 Amps Max.)
26 (70 Amps Max.)
t
t
10.0
20.0
5.0
8.33
16.67
4.165
Time in
Thermal Shock
Milliseconds
Operating Temperature
-40°C to +85°C
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: sales@carlingtech.com • www.carlingtech.com
|
6
C-Series - Agency Certifications
Agency Certifications:
UL Recognized
UL Standard 1077
Component Recognition Program
as Protectors, Supplementary
(Guide CCN/QVNU2, File E75596)
UL Standard 508
UL Standard 1500
Motor Controllers, Manual
(Guide CCN/NLRV2, File E135367)
Protectors, Supplementary for
Marine Electrical & Fuel Systems
(Guide PEQZ2, File E75596)
Ignition Protection
UL Listed
UL Standard 489
Circuit Breakers, Molded Case,
(Guide DIVQ, File E129899)
UL Standard 489A
Communications Equipment
(Guide CCN/DITT, File E189195)
CSA Accepted
Component Supplementary Protector
under Class 3215 30,
File 047848 0 000
CSA Standard C22.2 No. 235
CSA Certified
Circuit Breaker Model Case
(Class 1432 01, File 093910),
CSA Standard C22.2 No. 5.1 - M
TUV Certified
VDE Certified
EN60934, under License No.
R72041016
EN60934, VDE 0642 under File No.
10537
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: sales@carlingtech.com • www.carlingtech.com
|
C-Series Handle UL Recognized – Ordering Scheme
7
C A 3 — B 0 — 10 — 450 — 1 2 1 — C
8
9
10
11
Agency
Approval
1
2
3
4
5
6
7
Terminal
Actuator
Color
Mounting
Bezel/Barrier
Series
Actuator
Poles
Circuit
Aux/Alarm
Switch
Frequency
& Delay
Current Rating
7 CURRENT RATING (AMPERES)
1 SERIES
C
CODE AMPERES
020 0.020
025 0.025
030 0.030
035 0.035
040 0.040
045 0.045
050 0.050
055 0.055
060 0.060
065 0.065
070 0.070
075 0.075
080 0.080
085 0.085
090 0.090
095 0.095
210 0.100
215 0.150
220 0.200
225 0.250
230 0.300
235 0.350
240 0.400
245 0.450
250 0.500
255 0.550
260 0.600
265 0.650
270 0.700
275 0.750
280 0.800
285 0.850
290 0.900
295 0.950
410 1.000
512 1.250
415 1.500
517 1.750
420 2.000
522 2.250
425 2.500
527 2.750
430 3.000
614 14.000
615 15.000
616 16.000
617 17.000
618 18.000
620 20.000
622 22.000
624 24.000
625 25.000
630 30.000
635 35.000
640 40.000
650 50.000
6609 60.000
6709 70.000
6809 80.000
6859 85.000
6909 90.000
6959 95.000
8109 100.000
435 3.500
440 4.000
445 4.500
450 5.000
455 5.500
460 6.000
465 6.500
470 7.000
475 7.500
480 8.000
485 8.500
490 9.000
495 9.500
610 10.000
710 10.500
611 11.000
711 11.500
612 12.000
712 12.500
613 13.000
2 ACTUATOR1
A
B
S
T
Handle, one per pole
Handle, one per multipole unit
Mid-Trip Handle, one per pole
Mid-Trip, one per pole & Alarm Switch
3 POLES2
1
2
One
Two
3
4
Three
Four
5
6
Five
Six
4 CIRCUIT3
F4
Relay Trip (current)
Relay Trip (voltage)
A3
B
Switch Only (no coil)
G4
Series Trip (current)
Series Trip (voltage)
Shunt Trip (current)
Shunt Trip (voltage)
H4,5 Dual Coil with Shunt Trip
Voltage Coil
C
D4
E4
K4,5 Dual Coil with Relay Trip
Voltage Coil
VOLTAGE COIL (NORMINAL RATED VOLTAGE)7
5 AUXILIARY/ALARM SWITCH
CODE
RATING
0
2
3
4
without Aux Switch
6
8
9
S.P.S.T., 0.139 Solder Lug
S.P.S.T., 0.187 Q.C. Terminal
S.P.D.T., 0.187 Q.C. Terminal
A06 6DC
A12 12DC
A18 18DC
A24 24DC
A32 32DC
A48 48DC
A65 65DC
J06 6AC
J12 12AC
J18 18AC
J24 24AC
J48 48AC
J65 65AC
K20 120AC
L40 240AC
S.P.D.T., 0.110 Q.C. Terminal
S.P.D.T., 0.139 Solder Lug
S.P.D.T., 0.110 Q.C. Terminal
(Gold Contacts)
8 TERMINAL15
612
Screw M6, threaded
6 FREQUENCY & DELAY
110
211
312
411
511
Stud 10-32, threaded
713,15
815
0.250 Double Click Connect
1/4” Clip Terminal
7/16” Clip Terminal
Plug-In Stud
033
107
11
DC 50/60Hz, Switch Only
DC Instantaneous
DC Ultra Short
DC Short
DC Medium
DC Long
50/60Hz Instantaneous
50/60Hz Ultra Short
50/60Hz Short
50/60Hz Medium
50/60Hz Long
30
31
32
34
DC 50/60Hz Instantaneous
DC 50/60Hz Ultra Short
DC 50/60Hz Short
DC 50/60Hz Medium
DC 50/60Hz Long
50/60Hz Short, Hi-Inrush
50/60Hz Medium, Hi-Inrush
50/60Hz Long, Hi-Inrush
DC Short, Hi-Inrush
DC Medium, Hi-Inrush
DC Long, Hi-Inrush
Screw 10-32
Screw 1/4-20, threaded
Screw M5 x 0.8, threaded
Screw M5 x 0.8
912,15
A14
12
14
16
207
21
22
24
26
C11,15
5/16” Clip Terminal
36
428
448
468
528
548
56
9 ACTUATOR COLOR & LEGEND16
Actuator Color
I-O
A
C
F
H
K
M
P
R
T
ON-OFF
Dual
1
Legend Color
Black
White
B
D
G
J
Black
2
White
Red
3
White
Green
4
White
Notes:
Actuator Code:
Blue
L
5
White
1
A: Handle tie pin spacer(s) and retainers provided assembled with multi-pole units.
B: Handle location as viewed from front of breaker:
Yellow
N
Q
S
U
6
Black
Gray
7
Black
2 pole - left pole
5 pole - three handles at center poles
3 pole - center pole
4 pole - two handles at center poles
6 pole - four handles at center poles
Orange
8
Black
Black (short handle)17
9
White
S: Handle moves to mid-position only upon electrical trip of the breaker. Available with
circuit codes B, C, D, E, F, G, H and K.
T: Handle moves to mid-position and alarm switch activates only upon electrical trip of
the breaker. Available with circuit codes B & C.
10 MOUNTING/BARRIERS
MOUNTING STYLE
Threaded Insert
BARRIERS
VOLTAGE
Standard multipole units have all poles identical except when specifying auxilary switch
and/or mixed poles. 4 pole max w/VDE. 5th pole available as Series Trip w/Voltage Coil only.
Switch Only circuits, rated up to 50 amps and 6 poles, and only available with VDE Certi-
fication when tied to a protected pole (Circuit Code B, C, D or H.). For .02 to 30 amps,
select Current Code 630. For 35 - 50 amps, select Current Code 650. For 55-70 amps,
select Current Code 670. For 75-100 amps, select Current Code 810.
Circuit Codes D,E,F,G,H & K available with Terminal Codes 1,2,4 & 5 only. Circuit Codes
D, F, H & K available up to 50 amps maximum Current Rating.
Consult factory for available Dual Coil options, as special catalog number is required.
Dual Coil Voltage Coils with Shunt Trip Construction trip instantaneously on line voltage.
Dual Coil Voltage Coils require 30VA minimum power to trip instantaneously and are
rated for intermittent duty only.
2
3
<
<
1
6-32 x 0.195 inches
6-32 x 0.195 inches
6-32 x 0.195 inches
ISO M3 x 5mm
no
300
300
300
300
300
300
A
yes
yes
no
C18
2
>
–
<
<
B
ISO M3 x 5mm
yes
yes
4
5
D18
ISO M3 x 5mm
>
–
Front Panel Snap-In, 1.00” [25.4mm] wide bezel
E17
with Handleguard
no
300
<
ers, one aux. switch is supplied, mounted in the extreme right pole.
Voltage coils not rated for continuous duty. Available only with delay codes 10 and 20.
Available with Circuit Codes B & D only, and up to 50 amps maximum.
Current Ratings 60 - 70 are available up to four poles maximum. Ratings 71 - 100 are
available up to two poles maximum.
6
UL Recognized, CSA Accepted
7
8
9
Terminal Code 1 available to 60 amps maximum.
Terminal Codes 2,4,5 and C available to 50 amps maximum.
Terminal Codes 3,6 & 9 available to 100 amps maximum.
10
11
12
13
14
15
16
Terminal Code 7 available to 25 amps maximum.
Terminal Code A available to 100 amps maximum.
Terminal Codes 7,8,9 & C are not VDE approved.
No marking available. Consult factory. VDE/TUV Approval requires dual (I-O, ON-OFF)
or I-O markings on all handles.
Single pole only.
VDE/TUV: 30 amps max.; UL/CSA: 50 amps max.; Available in 2 - 4 poles only and
limited to AC Delays. “General Purpose amps” not rated for “full load amps” or to be
used in applications with a motor.
17
18
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: sales@carlingtech.com • www.carlingtech.com
|
8
C-Series Handle Parallel Pole UL489A Listed – Ordering Scheme
C A 2 — P 0 — D4 — 820 — 3 2 1 — M T
8
9
10
Mounting
11
12
1
2
3
4
5
6
7
Terminal
Actuator
Color
Max. App. Agency
Rating Approval
Series
Actuator
Poles
Circuit
Aux/Alarm
Switch
Frequency
& Delay
Current Rating
8 TERMINAL2
1 SERIES
3
6
A
1/4-20, threaded
C
M6, threaded
Plug-In Stud
2 ACTUATOR1
A
S
T
Handle, one per pole
Mid-Trip Handle, one per pole
Mid-Trip, one per pole & Alarm Switch
9 ACTUATOR COLOR
LEGEND
ON-OFF
Dual
Legend Color
Black
White
Black
Red
B
D
G
J
1
2
3
4
5
6
7
8
3 POLES3
White
2
Two
3
Three
White
Green
Blue
White
L
White
4 CIRCUIT
Yellow
Gray
N
Q
S
Black
P
Series Trip (parallel pole)
Black
Orange
Black
5 AUXILIARY/ALARM SWITCH
0
2
3
4
without Aux Switch
6
8
9
S.P.S.T., 0.139 Solder Lug
S.P.S.T., 0.187 Q.C. Terminal
S.P.D.T., 0.187 Q.C. Terminal
10 MOUNTING/BARRIERS
MOUNTING STYLE
Threaded Insert
S.P.D.T., 0.110 Q.C. Terminal
S.P.D.T., 0.139 Solder Lug
S.P.D.T., 0.110 Q.C. Terminal
(Gold Contacts)
1
2
6-32 x 0.195 inches
ISO M3 x 5mm
6 FREQUENCY & DELAY
11 MAXIMUM APPLICATION RATING
80 DC
D1
D2
DC Ultra Short
DC Short
D4
D6
DC Medium
DC Long
M
12 AGENCY APPROVAL
7 CURRENT RATING (AMPERES)
T
K
7
UL489A Listed (up to 250 amps)
CODE AMPERES
UL489A Listed, VDE Certified (up to 200 amps)
UL489A Listed, TUV Certified (up to 250 amps)
811 110.000
812 120.000
912 125.000
813 130.000
814 140.000
815 150.000
816 160.000
817 170.000
917 170.000
818 180.000
819 190.000
820 200.000
9223 225.000
8253 250.000
Notes:
1
Actuator Code:
A: Handle tie pin spacer(s) and retainers provided assembled with multi-pole units.
S: Handle moves to mid-position only upon electrical trip of the breaker.
T: Handle moves to mid-position and alarm switch activates only upon electrical trip of
the breaker.
2
3
Terminal Code:
3 & 6: Supplied with bus bars connecting the Line and Load Terminals.
A: Line and Load Terminals must be connected to a copper bus bar having a minimum
cross section of 0.078 square inches.
Above 200 amps, 3 poles are required.
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: sales@carlingtech.com • www.carlingtech.com
|
C-Series Handle UL489 Listed – Ordering Scheme
9
C A 3 — B 0 — 14 — 450 — 1 2 1 — K G
8
9
10
Mounting/
Barriers
11
12Agency
1
2
3
4
5
6
7
Terminal
Actuator
Color
Max. App. Approval
Rating
Series
Actuator
Poles
Circuit
Aux/Alarm
Switch
Frequency
& Delay
Current Rating
7 CURRENT RATING (AMPERES)5
1 SERIES
C
CODE AMPERES
210 0.100
215 0.150
220 0.200
225 0.250
230 0.300
235 0.350
240 0.400
245 0.450
250 0.500
255 0.550
260 0.600
265 0.650
270 0.700
275 0.750
280 0.800
285 0.850
290 0.900
295 0.950
410 1.000
512 1.250
415 1.500
517 1.750
420 2.000
522 2.250
425 2.500
527 2.750
430 3.000
435 3.500
440 4.000
445 4.500
450 5.000
455 5.500
460 6.000
465 6.500
470 7.000
475 7.500
480 8.000
485 8.500
490 9.000
495 9.500
610 10.000
710 10.500
611 11.000
711 11.500
612 12.000
712 12.500
613 13.000
614 14.000
615 15.000
616 16.000
617 17.000
618 18.000
620 20.000
622 22.000
624 24.000
625 25.000
630 30.000
635 35.000
640 40.000
660 60.000
670 70.000
680 80.000
685 85.000
690 90.000
695 95.000
810 100.000
2 ACTUATOR1
A
B
S
T
Handle, one per pole
Handle, one per multipole unit
Mid-Trip Handle, one per pole
Mid-Trip, one per pole & Alarm Switch
3 POLES2
1
One
2
Two
3
Three
4 CIRCUIT
B
Series Trip (current)
5 AUXILIARY/ALARM SWITCH3
0
2
3
4
without Aux Switch
6
8
9
S.P.S.T., 0.139 Solder Lug
S.P.S.T., 0.187 Q.C. Terminal
S.P.D.T., 0.187 Q.C. Terminal
8 TERMINAL6
69
8
Screw M6, threaded
1/4” Clip Terminal
7/16” Clip Terminal
Plug-In Stud
S.P.D.T., 0.110 Q.C. Terminal
S.P.D.T., 0.139 Solder Lug
S.P.D.T., 0.110 Q.C. Terminal
(Gold Contacts)
17
28
39
48
58
Stud 10-32, threaded
Screw 10-32
Screw 1/4-20, threaded
Screw M5 x 0.8, threaded
Screw M5 x 0.8
99
A10
C
5/16” Clip Terminal
6 FREQUENCY & DELAY
26
50/60Hz Long
11
12
14
16
21
22
24
DC Ultra Short
DC Short
424
444
464
524
544
564
50/60Hz Short, Hi-Inrush
50/60Hz Medium, Hi-Inrush
50/60Hz Long, Hi-Inrush
DC Short, Hi-Inrush
DC Medium, Hi-Inrush
DC Long, Hi-Inrush
9 ACTUATOR COLOR & LEGEND11
DC Medium
DC Long
50/60Hz Ultra Short
50/60Hz Short
50/60Hz Medium
Actuator Color
White
ON-OFF
Dual
Legend Color
Black
B
D
G
J
1
2
3
4
5
6
7
8
Black
White
Red
White
Green
Blue
White
L
White
Yellow
Gray
N
Q
S
Black
Notes:
1
Actuator Code:
Black
A: Handle tie pin spacer(s) and retainers provided assembled with multi-pole units.
B: Handle located, as viewed from front of breaker in left pole. 2 pole maximum.
S: Handle moves to mid-position only upon electrical trip of the breaker.
T: Handle moves to mid-position and alarm switch activates only upon electrical trip of
the breaker.
Orange
Black
10 MOUNTING/BARRIERS
MOUNTING STYLE
Threaded Insert
BARRIERS12
2
Standard multipole units have all poles identical except when specifying auxiliary switch
and/or mixed poles.
2 & 3 pole circuit breakers required for 120/240 VAC (Maximum application rating code
C) applications, have all poles identical except when specifying auxiliary / alarm switch
which is normally supplied in extreme right pole per figure B. Terminal barriers are
required on all multipole breakers.
1
2
6-32 x 0.195 inches
ISO M3 x 5mm
yes
yes
Third pole is for 120/240 VAC applications requiring neutral disconnect. The 3rd pole has
the same construction as poles 1 & 2.
11 MAXIMUM APPLICATION RATING
3
On multi-pole breakers, one auxiliary. switch is supplied, mounted in the extreme right
pole.
A
B
C
D
F
K
M
65 DC
125 DC
120/240 AC2
240 AC
277 AC
120 AC
80 DC
VDE approval on auxiliary switch codes 2, 3 & 4 only.
Auxiliary / Alarm Switch with Independent Circuit ie: separate from breaker circuit,
only available with circuit breakers rated 50 amp maximum at 80 VDC, 125 VDC, and
120 VAC. Auxiliary / Alarm Switch with Dependent Circuit ie: same as circuit breaker,
is supplied from factory with common terminal of auxiliary / alarm switch connected to
line terminal on 120/240 and 240 VAC ratings. Circuit breakers rated 120 VAC 50 amp
maximum can be supplied with Auxiliary/Alarm switch common terminal connected to
breaker line terminal. Consult factory for special catalog number.
Available up to 50 amps maximum.
4
5
Current ratings 71 - 100 with VDE approvals are available up to two poles maximum.
Terminal Codes 8, 9 & C are not VDE approved.
12 AGENCY APPROVAL11
6
A
F
G
J
without approvals
7
Terminal Code 1 available to 60 amps maximum.
UL489 Listed, VDE Certified, CSA Accepted
UL489 Listed, CSA Accepted
8
Terminal Codes 2, 4, 5 & C available to 50 amps maximum.
Terminal Codes 3, 6 & 9 available to 100 amps maximum.
9
UL489 Listed, TUV Certified, CSA Accepted
10
11
12
Terminal Code A available to 100 amps maximum.
VDE and TUV approvals require Dual (I-O, ON-OFF) markings on all handles.
Barriers supplied on multi-pole units only.
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: sales@carlingtech.com • www.carlingtech.com
|
10 C-Series Sealed Toggle UL Recognized – Ordering Scheme
C M 3 — B 0 — 10 — 450 — 1 0 1 — C
8
9
10
11
Agency
Approval
1
2
3
4
5
6
7
Terminal
Legend
Plate
Mounting
Bezel/Barrier
Series
Actuator
Poles
Circuit
Aux/Alarm
Switch
Frequency
& Delay
Current Rating
7 CURRENT RATING (AMPERES)9
1 SERIES
C
CODE AMPERES
020 0.020
025 0.025
030 0.030
035 0.035
040 0.040
045 0.045
050 0.050
055 0.055
060 0.060
065 0.065
070 0.070
075 0.075
080 0.080
085 0.085
090 0.090
095 0.095
210 0.100
215 0.150
220 0.200
225 0.250
230 0.300
235 0.350
240 0.400
245 0.450
250 0.500
255 0.550
260 0.600
265 0.650
270 0.700
275 0.750
280 0.800
285 0.850
290 0.900
295 0.950
410 1.000
512 1.250
415 1.500
517 1.750
420 2.000
522 2.250
425 2.500
527 2.750
430 3.000
614 14.000
615 15.000
616 16.000
617 17.000
618 18.000
620 20.000
622 22.000
624 24.000
625 25.000
630 30.000
635 35.000
640 40.000
650 50.000
6609 60.000
6709 70.000
6809 80.000
6859 85.000
6909 90.000
6959 95.000
8109 100.000
435 3.500
440 4.000
445 4.500
450 5.000
455 5.500
460 6.000
465 6.500
470 7.000
475 7.500
480 8.000
485 8.500
490 9.000
495 9.500
610 10.000
710 10.500
611 11.000
711 11.500
612 12.000
712 12.500
613 13.000
2 ACTUATOR1
M
Sealed Toggle, one per pole
3 POLES
1
One
2
Two
3
Three
4 CIRCUIT
F3
Relay Trip (current)
A2
B
Switch Only (no coil)
G3
Relay Trip (voltage)
Series Trip (current)
Series Trip (voltage)
Shunt Trip (current)
Shunt Trip (voltage)
H3,4 Dual Coil with Shunt Trip
Voltage Coil
C
D3
E3
K3,4 Dual Coil with Relay Trip
Voltage Coil
5 AUXILIARY/ALARM SWITCH
0
2
3
4
without Aux Switch
6
8
9
S.P.S.T., 0.139 Solder Lug
S.P.S.T., 0.187 Q.C. Terminal
S.P.D.T., 0.187 Q.C. Terminal
S.P.D.T., 0.110 Q.C. Terminal
S.P.D.T., 0.139 Solder Lug
S.P.D.T., 0.110 Q.C. Terminal
(Gold Contacts)
VOLTAGE COIL (NORMINAL RATED VOLTAGE)7
CODE
RATING
A06 6DC
A12 12DC
A18 18DC
A24 24DC
A32 32DC
A48 48DC
A65 65DC
J06 6AC
J12 12AC
J18 18AC
J24 24AC
J48 48AC
J65 65AC
K20 120AC
L40 240AC
6 FREQUENCY & DELAY
032
106
11
12
14
16
206
21
22
24
26
DC 50/60Hz, Switch Only
DC Instantaneous
DC Ultra Short
DC Short
DC Medium
DC Long
50/60Hz Instantaneous
50/60Hz Ultra Short
50/60Hz Short
50/60Hz Medium
50/60Hz Long
30
31
32
34
DC 50/60Hz Instantaneous
DC 50/60Hz Ultra Short
DC 50/60Hz Short
DC 50/60Hz Medium
DC 50/60Hz Long
50/60Hz Short, Hi-Inrush
50/60Hz Medium, Hi-Inrush
50/60Hz Long, Hi-Inrush
DC Short, Hi-Inrush
DC Medium, Hi-Inrush
DC Long, Hi-Inrush
8 TERMINAL
611
712
8
Screw M6, threaded
19
Stud 10-32, threaded
Screw 10-32
Screw 1/4-20, threaded
Screw M5 x 0.8, threaded
Screw M5 x 0.8
0.250 Double Click Connect
1/4” Clip Terminal
7/16” Clip Terminal
Plug-In Stud
36
210
311
410
510
427
447
467
527
547
56
911
A13
C10
5/16” Clip Terminal
9 LEGENDPLATE
No Legend
0
Notes:
1
Actuator Code M: Handle location as viewed from front of breaker:
2 pole - right pole 3 pole - center pole
2
Switch Only circuits, rated up to 50 amps and 3 poles, and only available with VDE. For
.02 to 30 amps, select Current Code 630. For 35 - 50 amps, select Current Code 650.
For 55-70 amps, select Current Code 670. For 75-100 amps, select Current Code 810.
Circuit Codes D,E,F,G,H & K available with Terminal Codes 1,2,4 & 5 only.
Consult factory for available Dual Coil options, as special catalog number is required.
Dual Coil Voltage Coils with Shunt Trip Construction trip instantaneously on line voltage.
Dual Coil Voltage Coils require 30VA minimum power to trip instantaneously and are
rated for intermittent duty only.
10 MOUNTING/BARRIERS
MOUNTING STYLE
BARRIERS
no
yes
1
A
Standard Hex Nut
3
4
Standard Hex Nut (multi-pole units only)
11 AGENCY APPROVAL
5
Auxiliary Switch available with Series Trip and Switch Only circuits. On multi-pole break-
ers, one aux. switch is supplied, mounted in the extreme right pole.
Voltage coils not rated for continuous duty. Available only with delay codes 10 and 20.
Available with Circuit Codes B & D only, and up to 50 amps maximum.
Consult factory for current ratings 71-100, in three pole units, available as special
catalog number only.
C
L
I
UL Recognized, CSA Accepted
UL Recognized, CSA Accepted with listed construction
UL Recognized, CSA Accepted, UL1500 ignition protection
6
7
8
9
10
11
12
13
Terminal Code 1 available to 60 amps maximum.
Terminal Codes 2,4,5 and C available to 50 amps maximum.
Terminal Codes 3,6 & 9 available to 100 amps maximum.
Terminal Code 7 available to 25 amps maximum.
Terminal Code A available to 100 amps maximum.
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: sales@carlingtech.com • www.carlingtech.com
|
C-Series Rocker UL Recognized – Ordering Scheme 11
C C 3 — B 0 — 14 — 450 — 1 2 1 — D
8
9
10
Mounting/
Barriers
11
Agency
Approval
1
2
3
4
5
6
7
Terminal
Actuator
Color
Series
Actuator
Poles
Circuit
Aux/Alarm
Switch
Frequency
& Delay
Current Rating
1 SERIES
C
7 CURRENT RATING (AMPERES)
CODE AMPERES
020 0.020
025 0.025
030 0.030
035 0.035
040 0.040
045 0.045
050 0.050
055 0.055
060 0.060
065 0.065
070 0.070
075 0.075
080 0.080
085 0.085
090 0.090
095 0.095
210 0.100
215 0.150
220 0.200
225 0.250
230 0.300
235 0.350
240 0.400
245 0.450
250 0.500
255 0.550
260 0.600
265 0.650
270 0.700
275 0.750
280 0.800
285 0.850
290 0.900
295 0.950
410 1.000
512 1.250
415 1.500
517 1.750
420 2.000
522 2.250
425 2.500
527 2.750
430 3.000
435 3.500
440 4.000
445 4.500
450 5.000
455 5.500
460 6.000
465 6.500
470 7.000
475 7.500
480 8.000
485 8.500
490 9.000
495 9.500
610 10.000
710 10.500
611 11.000
711 11.500
612 12.000
712 12.500
613 13.000
614 14.000
615 15.000
616 16.000
617 17.000
618 18.000
620 20.000
622 22.000
624 24.000
625 25.000
630 30.000
635 35.000
640 40.000
650 50.000
6609 60.000
6709 70.000
6809 80.000
6859 85.000
6909 90.000
6959 95.000
8109 100.000
2 ACTUATOR1
Single color
Two Color Visi-Rocker
J
K
L
Vertical legend
Horizontal legend
No legend
C
D
E
F
G
H
Indicate ON, vertical legend
Indicate ON, horizontal legend
Indicate ON, no legend
Indicate OFF, vertical legend
Indicate OFF, horizontal legend
Indicate OFF, no legend
Push-To-Reset, Single color
R
U
V
Vertical legend
Horizontal legend
No legend
Push-To-Reset, Visi-Rocker
N
O
P
Indicate OFF,
vertical legend
Indicate OFF,
horizontal legend
Indicate OFF,
no legend
VOLTAGE COIL (NORMINAL RATED VOLTAGE)7
CODE
RATING
A06 6DC
A12 12DC
A18 18DC
A24 24DC
A32 32DC
A48 48DC
A65 65DC
J06 6AC
J12 12AC
J18 18AC
J24 24AC
J48 48AC
J65 65AC
K20 120AC
L40 240AC
3 POLES2
1
One
2
Two
3
Three
8 TERMINAL
4 CIRCUIT
F4
Relay Trip (Current)
Relay Trip (Voltage)
110
211
312
411
511
612
Stud 10-32, threaded
713
8
0.250 Double Quick Connect
1/4” Clip Terminal
7/16” Clip Terminal
Plug-In Stud
A3 Switch Only (No Coil)
G4
Screw 10-32
B
Series Trip (Current)
Series Trip (Voltage)
Shunt Trip (Current)
Shunt Trip (Voltage)
H4,5 Dual Coil with Shunt Trip
Voltage Coil
Stud 1/4-20, threaded
Stud M5 x 0.8, threaded
Screw M5 x 0.8
9
C
A14
C
D4
E4
K4,5 Dual Coil with Relay Trip
Voltage Coil
5/16” Clip Terminal
Stud M6, threaded
5 AUXILIARY/ALARM SWITCH6
9 ACTUATOR COLOR & LEGEND16,17,18
Actuator or
0
2
3
4
without Aux Switch
6
8
9
S.P.S.T., 0.139 Solder Lug
S.P.S.T., 0.187 Q.C. Terminal
S.P.D.T., 0.187 Q.C. Terminal
S.P.D.T., 0.110 Q.C. Terminal
S.P.D.T., 0.139 Solder Lug
S.P.D.T., 0.110 Q.C. Terminal
(Gold Contacts)
Visi-Color Marking:
Marking Color:
Single Color
Rocker/Handle Visi-Rocker
Black
White
White
White
White
Black
Black
Black
Color:
White
Black
Red
I-O ON-OFF Dual/None
A
C
F
B
D
G
J
1
2
3
4
5
6
7
8
White
n/a
Red
6 FREQUENCY & DELAY
30
31
32
34
DC 50/60Hz Instantaneous
DC 50/60Hz Ultra Short
DC 50/60Hz Short
DC 50/60Hz Medium
DC 50/60Hz Long
50/60Hz Short, Hi-Inrush
50/60Hz Medium, Hi-Inrush
50/60Hz Long, Hi-Inrush
DC Short, Hi-Inrush
DC Medium, Hi-Inrush
DC Long, Hi-Inrush
Green
Blue
H
K
M
P
R
Green
Blue
Yellow
Gray
Orange
03
107
11
DC 50/60Hz, Switch Only
DC Instantaneous
DC Ultra Short
DC Short
DC Medium
DC Long
50/60Hz Instantaneous
50/60Hz Ultra Short
50/60Hz Short
50/60Hz Medium
50/60Hz Long
L
Yellow
Gray
Orange
N
Q
S
12
14
16
207
21
22
24
26
36
428
448
468
528
548
568
10 MOUNTING/BARRIERS1
Standard Rocker Bezel
6-32 x 0.195 inches
6-32 x 0.195 inches
6-32 x 0.195 inches
ISO M3 x 5mm
BARRIERS
no
1
yes
yes
no
2
319
4
Notes:
ISO M3 x 5mm
yes
yes
5
1
2
Push-To-Reset actuators have OFF portion of rocker shrouded.
619
ISO M3 x 5mm
Multi-pole breakers have all poles identical except when specifying Aux. switch and/or mixed poles, and have one
rocker per breaker. Rocker location as viewed from front panel: 2 pole – left pole; 3 pole – center pole.
Switch Only circuits, rated up to 50 amps and 3 poles, and only available with VDE Certification when tied to a
protected pole (Circuit Code B, C, D or H.), For .02 to 30 amps, select Current Code 630. For 35 - 50 amps, select
Current Code 650. For 55-70 amps, select Current Code 670. For 75-100 amps, select Current Code 810.
Circuit Codes D,E,F,G,H & K available with Terminal Codes 1,2,4 & 5 only. Circuit Codes D,F,H & K available up
to 50 amps maximum Current Rating.
Consult factory for available Dual Coil options, as special catalog number is required. Dual Coil Voltage Coils
with Shunt Trip Construction trip instantaneously on line voltage. Dual Coil Voltage Coils require 30VA minimum
power to trip instantaneously and are rated for intermittent duty only.
Auxiliary Switch available with Series Trip and Switch Only circuits. On multi-pole breakers, one aux. switch is
supplied, mounted in the extreme right pole.Auxilary switch codes 2,3 & 4 are VDE approved.
Voltage coils not rated for continuous duty. Available only with delay codes 10 and 20.
Available with Circuit Codes B & D only, and up to 50 amps maximum.
Current Ratings 60-70 are available up to four poles maximum. Ratings 71-100 are available up to two poles maximum.
Terminal Code 1 available to 60 amps maximum.
Terminal Codes 2,4,5 & C available to 50 amps maximum.
Terminal Codes 3,6 & 9 available to 100 amps maximum.
Terminal Code 7 available to 25 amps maximum.
Terminal Code A available to 100 amps maximum.
Terminal Codes 7,8,9 & C are not VDE approved.
Color shown is visi and legend with remainder of rocker black
Legend on Push-to-reset bezel/shroud is white when single color rocker is ordered. Dual = ON-OFF/I-O legend
with actuator codes C - G, and J, K, N, O, R, & U. None = no legend with actuator codes H, L, P, V. Rocker-
guard available with actuator codes C - L. Push-to-reset available witha ctuator codes N, O, P, R, U, V.
VDE/TUV approval requires Dual (I-O, ON-OFF) or I-O markings on rocker.
VDE/TUV: 30 amps max.; UL/CSA: 50 amps max.; Available in 2 - 4 poles only and limited to AC Delays.
“General Purpose amps” not rated for “full load amps” or to be used in applications with a motor.
Rockerguard Bezel
6-32 x 0.195 inches
6-32 x 0.195 inches
6-32 x 0.195 inches
ISO M3 x 5mm
3
no
A
yes
yes
no
C
E19
G
4
5
ISO M3 x 5mm
yes
yes
J
L19
ISO M3 x 5mm
Push-To-Reset Bezel
6-32 x 0.195 inches
6-32 x 0.195 inches
6-32 x 0.195 inches
ISO M3 x 5mm
no
B
yes
yes
no
D
6
7
8
F19
H
ISO M3 x 5mm
yes
yes
9
J
M19
10
11
12
13
14
15
16
17
ISO M3 x 5mm
11 AGENCY APPROVAL
C
D
E
H
I
UL Recognized, CSA Accepted
VDE Certified, UL Recognized, CSA Accepted
TUV Certified, UL Recognized, CSA Accepted
UL489 Construction: VDE Certified, UL Recognized, CSA Accepted
UL Rec. STD 1077, UL Rec. 1500 (ignition protected), CSA Accepted
UL489 Construction: UL Recognized, CSA Accepted
18
19
L
R
UL489 Construction: TUV Certified, UL Recognized, CSA Accepted
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: sales@carlingtech.com • www.carlingtech.com
|
12 C-Series Rocker UL Listed – Ordering Scheme
C C 3 — B 0 — 14 — 450 — 1 2 A — K G
8
9
10
Mounting/
Barriers
11
12
1
2
3
4
5
6
7
Terminal
Actuator
Color
Max. App. Agency
Rating Approval
Series
Actuator
Poles
Circuit
Aux/Alarm
Switch
Frequency
& Delay
Current Rating
7 CURRENT RATING (AMPERES)4
1 SERIES
C
CODE AMPERES
210 0.100
215 0.150
220 0.200
225 0.250
230 0.300
235 0.350
240 0.400
245 0.450
250 0.500
255 0.550
260 0.600
265 0.650
270 0.700
275 0.750
280 0.800
285 0.850
290 0.900
295 0.950
410 1.000
512 1.250
415 1.500
517 1.750
420 2.000
522 2.250
425 2.500
527 2.750
430 3.000
435 3.500
440 4.000
445 4.500
450 5.000
455 5.500
460 6.000
465 6.500
470 7.000
475 7.500
480 8.000
485 8.500
490 9.000
495 9.500
610 10.000
710 10.500
611 11.000
711 11.500
612 12.000
712 12.500
613 13.000
614 14.000
615 15.000
616 16.000
617 17.000
618 18.000
620 20.000
622 22.000
624 24.000
625 25.000
630 30.000
635 35.000
640 40.000
650 50.000
660 60.000
670 70.000
680 80.000
685 85.000
690 90.000
695 95.000
100 100.000
2 ACTUATOR1
Two Color Visi-Rocker
C
D
F
Indicate ON, vertical legend
Single color
Indicate ON, horizontal legend
Indicate OFF, vertical legend
Indicate OFF, horizontal legend
J
K
Vertical legend
Horizontal legend
G
ROCKER STYLE DESCRIPTIONS
INDICATE "ON"
INDICATE "OFF"
CODE "F"
SINGLE COLOR
CODE "C"
CODE "J"
CODE "K"
LINE
INDICATE
COLOR
LINE
LINE
LINE
LOCATION
CODE "D"
CODE "G"
LINE
LINE
8 TERMINAL
15
26
Stud 10-32, threaded
67
Stud M6, threaded
1/4” Clip Terminal
7/16” Clip Terminal
Plug-In Stud
Screw 8-32 w/saddle &
88
3 POLES1
washer clamps
97,8
A7,8
C6,8
37
46
56
Stud 1/4-20, threaded
Stud M5 x 0.8, threaded
Screw M5 x 0.8 w/saddle &
washer clamps
1
One
2
Two
3
Three
5/16” Clip Terminal
4 CIRCUIT
B
Series Trip (current)
9 ACTUATOR COLOR & LEGEND11
Actuator or
5 AUXILIARY/ALARM SWITCH2
0
2
3
4
without Aux Switch
6
8
9
S.P.S.T., 0.139 Solder Lug
S.P.S.T., 0.187 Q.C. Terminal
S.P.D.T., 0.187 Q.C. Terminal
Visi-Color 9 Marking:
Marking Color:
Single Color
Rocker/Handle Visi-Rocker
Black
White
White
White
White
Black
Black
Black
S.P.D.T., 0.110 Q.C. Terminal
S.P.D.T., 0.139 Solder Lug
S.P.D.T., 0.110 Q.C. Terminal
(Gold Contacts)
Color:
White
Black
Red
ON-OFF
Dual10
B
D
G
J
1
2
3
4
5
6
7
8
White
n/a
Red
Green
Blue
Green
Blue
Yellow
Gray
Orange
6 FREQUENCY & DELAY
26
50/60Hz Long
L
11
12
14
16
21
22
24
DC Ultra Short
DC Short
DC Medium
428
448
468
528
548
56
50/60Hz Short, Hi-Inrush
50/60Hz Medium, Hi-Inrush
50/60Hz Long, Hi-Inrush
DC Short, Hi-Inrush
DC Medium, Hi-Inrush
DC Long, Hi-Inrush
Yellow
Gray
Orange
N
Q
S
DC Long
50/60Hz Ultra Short
50/60Hz Short
50/60Hz Medium
10 MOUNTING/BARRIERS12
Standard Rocker Bezel
Threaded Insert, 2 per pole
6-32 x 0.195 inches
ISO M3 x 5mm
BARRIERS13
Notes:
A
C
yes
yes
1
Multi-pole breakers have all breakers identical except when specifying Aux. switch and/
or mixed poles, and have one rocker per breaker.
Rockerguard Bezel
Threaded Insert, 2 per pole
6-32 x 0.195 inches
ISO M3 x 5mm
2
3
4
On multi-pole breakers, one aux. switch is supplied, mounted in the extreme right pole.
Available up to 50 amps maximum.
Current ratings 71 - 100 with VDE approvals are available up to two poles maximum.
Terminal Code 1 available to 60 amps maximum.
B
D
yes
yes
5
6
7
8
Terminal Codes 2, 4, 5 & C available to 50 amps maximum.
Terminal Codes 3, 6, 9 & A available to 100 amps maximum.
Terminal Codes 8, 9 & C are not VDE approved.
11 MAXIMUM APPLICATION RATING
9
Color shown is visi and legend with remainder of rocker black
Dual = ON-OFF/I-O legend on actuator.
VDE and TUV approval requires Dual (I-O, ON-OFF) markings on rocker.
Rockerguard available with all actuator codes.
Barriers supplied on multi-pole units only.
2 & 3 pole circuit breakers required for 120/240 AC rating.
A
B
C
D
F
65 DC
10
11
12
13
14
125 DC
120/240 AC14
240 AC
277 AC
120 AC
80 DC
K
M
12 AGENCY APPROVAL
A
F
G
J
without approvals
UL 489 Listed, CSA Certified, & VDE Certified
UL 489 Listed & CSA Certified
UL489 Listed, CSA Certified & TUV Certified
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: sales@carlingtech.com • www.carlingtech.com
|
C-Series Flat Rocker UL Recognized – Ordering Scheme 13
C 1 2 — B 0 — 10 — 450 — 1 2 1 — E
8
9
10
Mounting/
Barriers
11
Agency
Approval
1
2
3
4
5
6
7
Terminal
Actuator
Color
Series
Actuator
Poles
Circuit
Aux/Alarm
Switch
Frequency
& Delay
Current Rating
1 SERIES
C
7 CURRENT RATING (AMPERES)9
CODE AMPERES
020 0.020
025 0.025
030 0.030
035 0.035
040 0.040
045 0.045
050 0.050
055 0.055
060 0.060
065 0.065
070 0.070
075 0.075
080 0.080
085 0.085
090 0.090
095 0.095
210 0.100
215 0.150
220 0.200
225 0.250
230 0.300
235 0.350
240 0.400
245 0.450
250 0.500
255 0.550
260 0.600
265 0.650
270 0.700
275 0.750
280 0.800
285 0.850
290 0.900
295 0.950
410 1.000
512 1.250
415 1.500
517 1.750
420 2.000
522 2.250
425 2.500
527 2.750
430 3.000
435 3.500
440 4.000
445 4.500
450 5.000
455 5.500
460 6.000
465 6.500
470 7.000
475 7.500
480 8.000
485 8.500
490 9.000
495 9.500
610 10.000
710 10.500
611 11.000
711 11.500
612 12.000
712 12.500
613 13.000
614 14.000
615 15.000
616 16.000
617 17.000
618 18.000
620 20.000
622 22.000
624 24.000
625 25.000
630 30.000
635 35.000
640 40.000
650 50.000
6609 60.000
6709 70.000
6809 80.000
6859 85.000
6909 90.000
6959 95.000
8109 100.000
2 ACTUATOR1
Two Color Visi-Rocker
1
2
Indicate OFF, vertical legend
Indicate OFF, horizontal legend
Single color
3
4
Vertical legend
Horizontal legend
Push-To-Reset, Visi-Rocker
5
6
Indicate OFF, vertical legend
Indicate OFF, horizontal legend
Push-To-Reset , Single color
7
8
Vertical legend
Horizontal legend
3 POLES2
1
One
2
Two
3
Three
VOLTAGE COIL (NORMINAL RATED VOLTAGE)7
CODE
RATING
A06 6DC
A12 12DC
A18 18DC
A24 24DC
A32 32DC
A48 48DC
A65 65DC
J06 6AC
J12 12AC
J18 18AC
J24 24AC
J48 48AC
J65 65AC
K20 120AC
L40 240AC
4 CIRCUIT
F4
Relay Trip (Current)
Relay Trip (Voltage)
A3 Switch Only (No Coil)
G4
B
Series Trip (Current)
Series Trip (Voltage)
Shunt Trip (Current)
Shunt Trip (Voltage)
H4,5 Dual Coil with Shunt Trip
Voltage Coil
C
D4
E4
K4,5 Dual Coil with Relay Trip
Voltage Coil
8 TERMINAL
612
713
8
Stud M6, threaded
110
211
312
411
511
Stud 10-32, threaded
0.250 Double Quick Connect
1/4” Clip Terminal
7/16” Clip Terminal
Plug-In Stud
Screw 10-32
5 AUXILIARY/ALARM SWITCH6
Stud 1/4-20, threaded
Stud M5 x 0.8, threaded
Screw M5 x 0.8
9
A14
C
0
2
3
4
without Aux Switch
6
8
9
S.P.S.T., 0.139 Solder Lug
S.P.S.T., 0.187 Q.C. Terminal
S.P.D.T., 0.187 Q.C. Terminal
S.P.D.T., 0.110 Q.C. Terminal
S.P.D.T., 0.139 Solder Lug
S.P.D.T., 0.110 Q.C. Terminal
(Gold Contacts)
5/16” Clip Terminal
9 ACTUATOR COLOR & LEGEND16,17,18
Actuator or
Visi-Color Marking:
Marking Color:
Single Color
Rocker/Handle Visi-Rocker
Black
White
White
White
White
Black
Black
Black
6 FREQUENCY & DELAY
30
31
32
34
DC 50/60Hz Instantaneous
DC 50/60Hz Ultra Short
DC 50/60Hz Short
DC 50/60Hz Medium
DC 50/60Hz Long
50/60Hz Short, Hi-Inrush
50/60Hz Medium, Hi-Inrush
50/60Hz Long, Hi-Inrush
DC Short, Hi-Inrush
DC Medium, Hi-Inrush
DC Long, Hi-Inrush
03
107
11
DC 50/60Hz, Switch Only
DC Instantaneous
DC Ultra Short
DC Short
DC Medium
DC Long
50/60Hz Instantaneous
50/60Hz Ultra Short
50/60Hz Short
50/60Hz Medium
50/60Hz Long
Color:
White
Black
Red
I-O ON-OFF Dual/None
A
C
F
H
K
M
P
R
B
D
G
J
1
2
3
4
5
6
7
8
White
n/a
12
14
16
207
21
22
24
26
36
Red
428
448
468
528
548
568
Green
Blue
Green
Blue
L
Yellow
Gray
N
Q
S
Yellow
Gray
Orange
Orange
10 MOUNTING/BARRIERS1
Notes:
1
2
Standard Rocker Bezel
6-32 x 0.195 inches
6-32 x 0.195 inches
6-32 x 0.195 inches
ISO M3 x 5mm
BARRIERS
VOLTAGE
Push-to-reset actuators have OFF portion of rocker shrouded.
<
<
no
300
300
300
300
300
300
1
Multi-pole breakers have all poles identical except when specifying Aux. switch and/or mixed poles, and have
one rocker per breaker. Rocker location as viewed from front panel: 2 pole – left pole; 3 pole – center pole.
Switch Only circuits, rated up to 50 amps and 3 poles, and only available with VDE Certification when tied to a
protected pole (Circuit Code B, C, D or H.). For .02 to 30 amps, select Current Code 630. For 35 - 50 amps,
select Current Code 650. For 55-70 amps, select Current Code 670. For 75-100 amps, select Current Code 810.
Circuit Codes D,E,F,G,H & K available with Terminal Codes 1,2,4 & 5 only. Circuit Codes D,F,H & K available up
to 50 amps maximum Current Rating.
Consult factory for available Dual Coil options, as special catalog number is required. Dual Coil Voltage Coils
with Shunt Trip Construction trip instantaneously on line voltage. Dual Coil Voltage Coils require 30VA minimum
power to trip instantaneously and are rated for intermittent duty only.
Auxiliary Switch available with Series Trip and Switch Only circuits. On multi-pole breakers, one aux. switch is
supplied, mounted in the extreme right pole.Auxilary switch codes 2,3 & 4 are VDE approved.
Voltage coils not rated for continuous duty. Available only with delay codes 10 and 20.
Available with Circuit Codes B & D only, and up to 50 amps maximum.
Current ratings 60-70 are available up to four poles maximum. Current ratings 71 - 100 are available up to two
poles maximum.
Terminal Code 1 available to 60 amps maximum.
Terminal Codes 2,4,5 & C available to 50 amps maximum.
Terminal Codes 3,6 & 9 available to 100 amps maximum.
Terminal Code 7 available to 25 amps maximum.
Terminal Code A available to 100 amps maximum.
Terminal Codes 7,8,9 & C are not VDE approved.
Color shown is visi & legend with remainder of rocker black. Dual = ON-OFF/I-O legend.
Legend on Push-to-reset bezel/shroud is white with single color actuator codes 7 & 8. Legend on Push-to-reset
bezel/shroud matches visi-color of rocker with actuator codes 5 & 6.
yes
yes
no
2
319
4
>
3
–
<
<
ISO M3 x 5mm
yes
yes
5
619
4
5
>
ISO M3 x 5mm
–
Recessed Off Rocker
6-32 x 0.195 inches
6-32 x 0.195 inches
6-32 x 0.195 inches
ISO M3 x 5mm
<
<
no
300
300
300
300
300
300
7
yes
yes
no
8
>
9
–
6
<
<
A
C
E
ISO M3 x 5mm
yes
yes
7
8
9
>
ISO M3 x 5mm
–
Push-To-Reset Bezel
6-32 x 0.195 inches
6-32 x 0.195 inches
6-32 x 0.195 inches
ISO M3 x 5mm
<
<
no
300
300
300
300
300
300
B
10
11
12
13
14
15
16
17
yes
yes
no
D
F19
H
>
–
<
<
ISO M3 x 5mm
yes
yes
J
M19
>
ISO M3 x 5mm
–
11 AGENCY APPROVAL
18
19
VDE/TUV approval requires Dual (I-O, ON-OFF) or I-O markings on rocker.
C
E
I
UL Recognized, CSA Accepted
VDE/TUV: 30 amps max.; UL/CSA: 50 amps max.; Available in 2 & 3 poles only and limited to AC Delays.
“General Purpose amps” not rated for “full load amps” or to be used in applications with a motor.
Recessed “OFF SIDE” available with actuator codes 1,2,3&4. Legends on rocker are available in ink stamping only.
TUV Certified, UL Recognized, CSA Accepted
UL Rec. STD 1077, UL Rec. 1500 (ignition protected), CSA Accepted
UL489 Construction: UL Recognized, CSA Accepted
20
L
R
UL489 Construction: TUV Certified, UL Recognized, CSA Accepted
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: sales@carlingtech.com • www.carlingtech.com
|
14 C-Series Flat Rocker UL Listed – Ordering Scheme
C 1 2 — B 0 — 14 — 450 — 1 2 A — K G
8
9
10
Mounting/
Barriers
11
12
1
2
3
4
5
6
7
Terminal
Actuator
Color
Max. App. Agency
Rating Approval
Series
Actuator
Poles
Circuit
Aux/Alarm
Switch
Frequency
& Delay
Current Rating
7 CURRENT RATING (AMPERES)5
1 SERIES
C
CODE AMPERES
210 0.100
215 0.150
220 0.200
225 0.250
230 0.300
235 0.350
240 0.400
245 0.450
250 0.500
255 0.550
260 0.600
265 0.650
270 0.700
275 0.750
280 0.800
285 0.850
290 0.900
295 0.950
410 1.000
512 1.250
415 1.500
517 1.750
420 2.000
522 2.250
425 2.500
527 2.750
430 3.000
435 3.500
440 4.000
445 4.500
450 5.000
455 5.500
460 6.000
465 6.500
470 7.000
475 7.500
480 8.000
485 8.500
490 9.000
495 9.500
610 10.000
710 10.500
611 11.000
711 11.500
612 12.000
712 12.500
613 13.000
614 14.000
615 15.000
616 16.000
617 17.000
618 18.000
620 20.000
622 22.000
624 24.000
625 25.000
630 30.000
635 35.000
640 40.000
650 50.000
660 60.000
670 70.000
680 80.000
685 85.000
690 90.000
695 95.000
100 100.000
2 ACTUATOR1
Two Color Visi-Rocker
1
2
Indicate OFF, vertical legend
Indicate OFF, horizontal legend
Single color
3
4
Vertical legend
Horizontal legend
Push-To-Reset, Visi-Rocker
5
6
Indicate OFF, vertical legend
Indicate OFF, horizontal legend
Push-To-Reset , Single color
7
8
Vertical legend
Horizontal legend
3 POLES2
1
One
2
Two
3
Three
8 TERMINAL
16
27
Stud 10-32, threaded .625 long
Screw 8-32 w/saddle &
washer clamps
68
Stud M6, threaded 17mm long
1/4” Clip Terminal
7/16” Clip Terminal
Plug-In Stud
89
4 CIRCUIT
98,9
A8,9
C7,9
B
Series Trip (current)
38
47
57
Stud 1/4-20, threaded .625 long
Stud M5 x 0.8, threaded .625 long
Screw M5 x 0.8 w/saddle &
washer clamps
5/16” Clip Terminal
5 AUXILIARY/ALARM SWITCH2
0
2
3
4
without Aux Switch
6
8
9
S.P.S.T., 0.139 Solder Lug
S.P.S.T., 0.187 Q.C. Terminal
S.P.D.T., 0.187 Q.C. Terminal
S.P.D.T., 0.110 Q.C. Terminal
S.P.D.T., 0.139 Solder Lug
S.P.D.T., 0.110 Q.C. Terminal
(Gold Contacts)
9 ACTUATOR COLOR & LEGEND12
Actuator or
Visi-Color 9 Marking:
Marking Color:
Single Color
6 FREQUENCY & DELAY
Color:
White
Black
Red
ON-OFF
Dual11
Rocker/Handle Visi-Rocker
11
12
14
16
21
22
24
DC Ultra Short
DC Short
26
50/60Hz Long
B
D
G
J
1
2
3
4
5
6
7
8
Black
White
White
White
White
Black
Black
Black
White
n/a
424
444
464
524
544
564
50/60Hz Short, Hi-Inrush
50/60Hz Medium, Hi-Inrush
50/60Hz Long, Hi-Inrush
DC Short, Hi-Inrush
DC Medium, Hi-Inrush
DC Long, Hi-Inrush
DC Medium
DC Long
50/60Hz Ultra Short
50/60Hz Short
50/60Hz Medium
Red
Green
Blue
Yellow
Gray
Orange
Green
Blue
L
Yellow
Gray
Orange
N
Q
S
Notes:
1
2
Push-to-reset actuators have OFF portion of rocker shrouded.
Multi-pole breakers have all breakers identical except when specifying Aux. switch and/
or mixed poles, and have one rocker per breaker.
On multi-pole breakers, one aux. switch is supplied, mounted in the extreme right pole.
Available up to 50 amps maximum.
Current ratings 71 - 100 with VDE approvals are available up to two poles maximum.
Terminal Code 1 available to 60 amps maximum.
Terminal Codes 2, 4, 5 & C available to 50 amps maximum.
Terminal Codes 3, 6, 9 & A available to 100 amps maximum.
Terminal Codes 8, 9 & C are not VDE approved.
Color shown is visi and legend with remainder of rocker black
Dual = ON-OFF/I-O legend on actuator.
VDE and TUV approval requires Dual (I-O, ON-OFF) markings on rocker.
Legend on push-to-reset bezel/shroud is white when single color rocker is ordered.
Legend on push-to-reset bezel/shroud matches visi-color of rocker with actuator codes
5 & 6.
10 MOUNTING/BARRIERS12
Standard Rocker Bezel
Threaded Insert, 2 per pole
6-32 x 0.195 inches
BARRIERS15
3
4
5
6
7
8
9
10
11
12
13
A
C
yes
yes
ISO M3 x 5mm
Recessed Off Rocker14
Threaded Insert, 2 per pole
6-32 x 0.195 inches
E
F
yes
yes
ISO M3 x 5mm
Push-To-Reset Bezel
Threaded Insert, 2 per pole
6-32 x 0.195 inches
B
D
yes
yes
ISO M3 x 5mm
14
Recessed “OFF-SIDE” available with actuator codes 1, 2, 3, & 4. Legends on rocker are
available in ink stamping only.
Barriers supplied on multi-pole units only.
11 MAXIMUM APPLICATION RATING
A
B
C
D
F
65 DC
15
16
125 DC
120/240 AC16
240 AC
277 AC
120 AC
80 DC
2 & 3 pole circuit breakers required for 120/240 AC rating.
K
M
12 AGENCY APPROVAL
A
G
J
without approvals
UL 489 Listed & CSA Certified
UL489 Listed, CSA Certified & TUV Certified
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: sales@carlingtech.com • www.carlingtech.com
|
C-Series Handle – Circuit & Terminal Diagrams 15
.960 [24.38]
.311 DIA [Ø7.90]
.558 [14.17]
Notes:
1
2
3
All dimensions are in inches [millimeters].
Tolerance ±.020 [.51] unless otherwise specified.
Available on Series Trip and Switch Only Circuits when called for on multi-pole units.
Only one aux. switch is normally supplied, as viewed in mulit-pole identification scheme.
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: sales@carlingtech.com • www.carlingtech.com
|
16 C-Series Handle – Circuit & Terminal Diagrams
LINE
LOAD
Notes:
1
2
3
4
All dimensions are in inches [millimeters].
Tolerance ±.020 [.51] unless otherwise specified.
Schematic shown represents current trip circuits.
Available only as special catalog number.
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: sales@carlingtech.com • www.carlingtech.com
C-Series Handle – Form & Fit Drawings |
17
LINE
LOAD
Notes:
1
2
All dimensions are in inches [millimeters].
Tolerance ±.020 [.51] unless otherwise specified.
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: sales@carlingtech.com • www.carlingtech.com
|
18 C-Series Handleguard – Form & Fit Drawings
LINE
LOAD
Notes:
1
2
All dimensions are in inches [millimeters].
Tolerance ±.020 [.51] unless otherwise specified.
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: sales@carlingtech.com • www.carlingtech.com
|
C-Series Parellel Pole – Form & Fit Drawings 19
LINE
LOAD
Notes:
1
2
All dimensions are in inches [millimeters].
Tolerance ±.020 [.51] unless otherwise specified.
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: sales@carlingtech.com • www.carlingtech.com
|
20 C-Series Sealed Toggle – Form & Fit Drawings
LINE
LOAD
Notes:
1
2
All dimensions are in inches [millimeters].
Tolerance ±.020 [.51] unless otherwise specified.
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: sales@carlingtech.com • www.carlingtech.com
|
C-Series Rocker – Circuit & Terminal Diagrams 21
LINE
LOAD
Notes:
1
2
3
All dimensions are in inches [millimeters].
Tolerance ±.020 [.51] unless otherwise specified.
Schematic shown represents current trip circuit.
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: sales@carlingtech.com • www.carlingtech.com
|
22 C-Series Rocker – Form & Fit Drawings
LINE
LOAD
Notes:
1
2
3
4
Dimensions apply to all variations shown. Notice that circuit breaker line and load terminal orientation on indicate OFF is opposite of indicate ON.
For pole orientation with horizontal legend, rotate front view clockwise 90°.
All dimensions are in inches [millimeters].
Tolerance ±.020 [.51] unless otherwise specified.
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: sales@carlingtech.com • www.carlingtech.com
|
C-Series Flat Rocker – Form & Fit Drawings 23
LINE
LOAD
Notes:
1
2
3
For pole orientation with horizontal legend, rotate front view clockwise 90°.
All dimensions are in inches [millimeters].
Tolerance ±.020 [.51] unless otherwise specified.
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: sales@carlingtech.com • www.carlingtech.com
Worldwide Headquarters
Carling Technologies, Inc.
60 Johnson Avenue • Plainville, CT 06062
Phone: (860) 793-9281 • Fax: (860) 793-9231
Email: sales@carlingtech.com • www.carlingtech.com
East Region Sales Office, CT • ersm@carlingtech.com
Midwest Region Sales Office, IL • mrsm@carlingtech.com
West Region Sales Office, CA • wrsm@carlingtech.com
Asia-Pacific Headquarters
Carling Technologies, Asia-Pacific Ltd.,
Kowloon, Hong Kong
Int + 852-2737-2277 • Fax: Int + 852-2736-9332
Email: sales@carlingtech.com.hk
Shenzhen, China • shenzhen@carlingtech.com
Shanghai, China • shanghai@carlingtech.com
Pune, India • india@carlingtech.com
Kaohsiung, Taiwan • taiwan@carlingtech.com
Yokohama, Japan • japan@carlingtech.com
Europe/Middle East/Africa Headquarters
Carling Technologies, Ltd.,
Devon, England
Int + 44 1392-364422 • Fax: Int + 44 1392-364477
Email: ltd.sales@carlingtech.com
GmbH, Germany • gmbh@carlingtech.com
SAS, France • sas@carlingtech.com
REV_CB_C_1212